Building Intelligence
|
Relative Humidity Sensor
|
Relative Humidity Sensors used in both indoor and outdoor investigative research and building science applications.
|
Overview
General Description
- Building envelope cavity validation
- Indoor and outdoor air quality analysis
- Verification of equipment status
- Drying progress
- Process control
- Hygrostat
Features
- Hermetic Housing
- Humidity calibrated within ±2% @55% RH
- Integrated Thermistor – MF52 pearl-shaped precision NTC thermistor (cable version)
- Small size
- Compatible with SMT Mobile and Industrial WiDAQ
- Full interchangeability
- High reliability and long term stability
- Not affected by water immersion
- Instantaneous de-saturation after long period in saturation phase
- Fast response time suitable for low voltage wireless applications.
- High resistance to chemicals
- Unique solid polymer structure
Specs
|
Electrical Characteristics |
|
|
Operating Voltage |
0V to 5VDC |
|
Sensing Element |
HTM2500 |
|
Environmental |
|
|
Operating Temperature |
-30° to 70°C |
|
Operating Humidity Range |
0% to 100% RH |
|
Storage Temperature |
-40° to 85°C |
|
Storage Humidity |
0% to 100% RH |
|
Humidity Characteristics |
|
|
Humidity Measuring Range |
1% to 99% RH |
|
Relative Humidity Accuracy (10 to 95% RH) |
±3 to ±5 %RH |
|
WiDAQ Supply Voltage |
5VDC |
|
Current Consumption |
0.4mA |
|
Temperature Coefficient (10°C to 50°C) |
±0.1 %RH/°C |
|
Average Sensitivity from 33% to 75% RH |
+25 mV/%RH |
|
Recovery time after 150 hours of condensation |
10 seconds |
|
Humidity Hysteresis |
±1.5 %RH |
|
Long term stability |
±0.5 %RH/yr |
|
Time Constant (at 63% signal, static) 33% to 76% RH |
5 seconds |
|
Thermistor Characteristics |
|
|
Rated Resistance R25 |
10 to 250 KΩ |
|
B Value (25/50°C) |
4150K |
|
Operating Temperature |
-55° to 125°C |
|
Tolerance |
1% |
|
Approvals/Regulatory |
|
|
Passed Meas-France qualification process |
Vibration, shock, storage temperatures, high temperature and humidity and ESD. |
|
Chemical conditions tested |
Salt atmosphere, SO2, NOx, NO, CO, Softener, Soap, Toluene, acids (H2SO4, HNO3, HCI), HMDS, insecticide, cigarette smoke. HTM255 is not light sensitive. |
Connectivity
HTM2500 to Audio Jack
Insert RH Sensor in WiDAQ AUX Port
HTM2500 to 8 Channel WiDAQ
HTM2500 Wiring to 8 Resistance 2 Voltage WiDAQ